Tate Raised Floor Systems (PDF) Airflow Performance Information (Paired with DirectAire Panel) Static Pressure (inH2O) | 0% Power (CFM) | 100% Power (CFM) | -0.08 | 1695 | - | -0.06 | 1806 | - | -0.05 | 1856 | - | -0.04 | 1902 | - | -0.02 | 1978 | - | 0.00 | 2000 | - | 0.02 | 2012 | 254 | 0.04 | 2061 | 365 | 0.05 | 2086 | 411 | 0.06 | 2111 | 452 | 0.08 | 2158 | 525 | 0.10 | 2199 | 590 | 0.12 | 2235 | 648 | 0.14 | 2263 | 702 | 0.16 | 2284 | 752 | 0.18 | 2297 | 799 | 0.20 | 2303 | 844 |
Airflow Performance Information (Paired with DirectAire AL Panel) Static Pressure (inH2O) | 0% Power (CFM) | 100% Power (CFM) | -0.08 | 1710 | - | -0.06 | 1815 | - | -0.05 | 1862 | - | -0.04 | 1920 | - | -0.02 | 1992 | - | 0.00 | 2020 | - | 0.02 | 2018 | 254 | 0.04 | 2110 | 340 | 0.05 | 2106 | 380 | 0.06 | 2140 | 470 | 0.08 | 2130 | 570 | 0.10 | 2158 | 722 | 0.12 | 2169 | 809 | 0.14 | 2290 | 910 | 0.16 | 2290 | 980 | 0.18 | 2319 | 1067 | 0.20 | 2325 | 1140 |
INCLUDED COMPONENTS - PowerAire Quad- S
- 4 x Tool-less String Hangers
- 4 x Alternative Corner Lock Hangers
- Temperature Monitoring Probe and Control Cable
- Zip Ties
- 6' Power Cord (200-240V) (IEC C14 inlet - NEMA L6-15R outlet required)
AIRFLOW PANEL OPTIONS - DirectAire
- DirectAire Al
- DirectAire X2
UNDERSTRUCTURE OPTIONS - 2' Bolted Stringer Steel System
- 4' Bolted Stringer Steel System
|