Tate Raised Floor Systems (PDF) Airflow Performance Information (Paired with DirectAire X2 Panel) Static Pressure (inH2O) | 0% Open (CFM) | 50% Open (CFM) | 100% Open (CFM) | .02 | 60 | 280 | 481 | .04 | 106 | 444 | 710 | .05 | 111 | 499 | 822 | .06 | 114 | 529 | 932 | .08 | 128 | 609 | 1107 | .10 | 151 | 672 | 1188 | .12 | 156 | 735 | 1310 | .14 | 165 | 780 | 1419 | .16 | 183 | 837 | 1486 | .18 | 196 | 891 | 1600 | .20 | 204 | 932 | 1679 |
*Cooling capacities were calculated using the following formula:(CFM x Capture Index %) / 126(CFM needed to cool 1kW @ 25ºF ?T)= kW per rack. UNDERSTRUCTURE OPTIONS - 2' Bolted Stringer Steel System
- 4' Bolted Stringer Steel System
AIRFLOW PANEL OPTIONS - DirectAire (24" and 60cm versions)
|