Per Inlet Power Sensing (PIPS) This Sentry PIPS Cabinet Distribution Unit (otherwise known as a PDU) combines all of the features of a Smart CDU with the ability to provide power monitoring per inlet/infeed. This information replaces branch circuit monitoring devices typically installed in the power distribution panel or remote power panel (RPP) with higher accuracy and lower cost monitoring of each circuit attached to the CDU. Meets or exceeds ANSI C12.1 for +/- 1% Billing Grade Accuracy (independently tested by UL). Monitoring Parameters: - Input current (A)
- voltage (V)
- power (kW)
- apparent power (VA)
- power consumption (W-hr)
- crest factor
- power factor
HTTP/HTTPs Web Configuration & Control Use the Sentry Web interface to configure each unit, including network settings, outlet naming & grouping, SNMP alerts for environmental & power thresholds and firmware updates. Network managers can easily use SNMP requests to retrieve information and control power for individual outlets. Also use the Web interface to control individual or group outlets and monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection. Integrated Temp/Humidity Probes & Environmental Monitoring Two (2) RJ-style connectors located on the face panel of the PDU's enclosure provide support for two (2) Integrated Temperature & Humidity Probes with ten-foot (10') cables provide real-time measurements in the data center cabinet.
An optional EMCU-1-1B Environmental Monitor allows up to (2) additional temperature & humidity probes (EMTH-1-1), (1) water sensor (EMWS-1-1), (4) dry contact closures, (1) analog-to-digital contact sensor. Includes (1) temperature/humidity probe with unit. Expansion Tower PDU Connect an Expansion Cabinet power distribution unit to any POPS Cabinet PDU to control two power input circuits and manage outlets (individual or groups) under 1 IP address - our exclusive strategy for managing dual power-supply servers High Retention Locking Receptacles All STV-3101 PDUs utilize high retention receptacles to provide additional security when used with conventional power cords. Each PDU is also fully compatible with Server Technology's locking power cord solutions (supplied separately). - 10/100 BaseT Ethernet
- HTTP/HTTPS
- SSLv3/TLSv1
- SNMPv2 and v3
- SSHv2
- Telnet
- LDAPv3/LDAPS
- TACACS+
- RADIUS
- RS-232 (Serial)
- IPv4 and IPv6
North American Certifications - cTUVus Mark to UL 60950-1: 2007 and CAN/CSA 22.2 No. 60950-1-07
- FCC Class A, Part 15
- CE Mark
- EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
Branch Circuit Protection Environmental Requirements - Operating Temperature: 32° to 140° F (0° to 60° C)
- Storage Temperature: -40° to 185° F (-40° to 85° C)
- Operating & Storage Relative Humidity: 8% to 90% non-condensing
|