Powerware PW5125-5000 Rackmount UPS Power

Please note, the Eaton PW5125-5000 (5125 UPS family) UPS has been discontinued and replaced by the Eaton 5P and 5PX series. For other upgrade options please contact us.

The Powerware PW5125-5000 delivers a space-saving 3U rack height package and is the ideal high-density power protection solution for your servers, storage systems, network equipment and other critical devices. UPS Models ship with both black and beige front panels.

Eaton Powerware PW5125-5000 Rackmount UPS Power

Eaton Powerware

PW 5125 5000 Specifications:

Mechanical  
Dimensions (HxWxD) 5.25 x 17.50 x 26.0 in. (133 x 445 x 661 mm.)
Weight 161 lbs. (73 kg.)
Electrical Input  
Power Rating 5000VA / 4500W
Nominal Voltage 200/208, 220, 230 and 240 Vac2
Input Voltage Ranges (for user-selectable voltages) 160-288
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 46-54 hz for 50 hz; 56-64 hz for 60 hz
Connections  
Input Connections (1) NEMA L6-30P
Output Receptacles IEC-320-C13(X 4) , NEMA L6-20R(X 2) , NEMA L6-30R(X 1)
Battery  
Battery Type Sealed, lead-acid; maintenance free
Battery Replacement Hot-swappable internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input
Electrical Output  
On Utility Voltage Regulation -10% to +6% of nominal
On Battery Voltage Regulation  ±5% RMS
Voltage Wave Shape (on battery) Sine Wave
Output Protection Short circuit protection
Communications  
User Interface Front Control Panel
Audible Alarms For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault
Network Transient Protector No
Communication Ports Native USB and serial port
Communication Slot Web/SNMPxHub card factory installed; other options also available
Cable 6-foot communications cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
General  
Electrical Power Module Replcmnt yes, hot-swap
Diagnostics full system self-test on power up
UPS Bypass Internal Bypass
Transfer Time 4ms typical, 6ms max
Overload (normal operation) 110% overload for 30 seconds short circuit protected
Environmental  
Operating Temperature 10°C to 40°C
Storage Temperature -25°C to 55°C
Relative Humidity 0% to 95% non-condensing
Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating high-energy 6500 A peak
Audible Noise less than 45 dBA typical
 Altitude 3000m (10,000 ft) without derating