Fail-Safe Transfer Switch CDU-PPTS, Basic, (8) C13 Outlets, 20A 100-240V
The Sentry Fail-Safe Transfer Switch (FSTS) features two input power feeds, from separate AC circuits, to supply single-power equipment with dual, redundant power sources. A primary AC circuit provides power to the connected device(s). With this rack automatic transfer switch, if the primary source becomes unavailable for whatever reason, then the Sentry FSTS auto-switches to the secondary power source to support the connected equipment.
Price $645.00
Dimensions
1U (1.75"H) x 17.2"W x 7"D
The transfer from one power source to the other is seamless to the connected equipment with this rack automatic transfer switch. When the secondary power source is available, an interruption of the primary power source will not affect the equipment's uptime or performance.
Unique to the Sentry FSTS is the ability to designate which power source is primary and which is secondary. With the Primary Select switch, a power engineer simply toggles the switch from primary to secondary, which transfers the load from one power feed to the other. Now, the "secondary" becomes "primary" and the power engineer can safely work on the first power source without dropping power to the connected equipment.
Also exclusive to the FSTS is the ability to select the high voltage (208-230V) or low voltage (110-120V) operating range of the AC power source. Use the Sentry FSTS as a universal power transfer switch for all cabinets and servers, regardless of the voltage. To apply power, just remove a panel and then choose the appropriate voltage range to the Fail-Safe Transfer Switch.
Input Power
(2) IEC 60329/C20 Inlets
Primary Power Source Input
Secondary Power Source Input
Requires both power input feeds to be phase-synchronized
Outlet Power
(8) IEC 60320/C13 outlets
Sum of all 8 outlets must be less than or equal to 16A
Each outlet rated by UL/CSA to 12A for 100-120V and 208-240V operation, and by TUV to 10A for 230V operation.
Indicator LEDs
Confirms power supplied to outlets
Identifies condition as primary power source or secondary power source supplying power to outlets
Transfer Range
Nominal
Pull In
Drop Out
110-120V
90V
12V
208-230V
173V
23V
Voltage Range Select
Supplies either 100-120V or 208-230V AC voltage ranges
120V and 230V equipment cannot be intermixed
All power input feeds must be removed prior to selecting/altering operating range
Remove Range Select faceplate covering to select appropriate voltage
Lucite window allows visual confirmation of voltage range
Switch in "up" position designates 208/230V
Switch in "down" position indicates 110/120VNominal
Mechanical Integrity
Dual-brace cable retainer brackets on power input feeds
Clip-style cable-retention retainer brackets at each power outlet
Adjustable mounting for the front or rear flush panel
Conformance & Agency Certifications
US & Canada (cTUVus mark) to UL 60950-1:2003 and CAN/CSA 22.2 No. 60950-1-03
European Union (TUVGS mark) to EN 60950-1:2001
FCC Class A, Part 15; CE; EMC - EN 55022 Class A, EN 55024