The APC NetBotz Rack Sensor Pod 150 (NBPD0150) connects to a NetBotz appliance and allows you to increase the space monitored by your NetBotz security and environmental monitoring system. The NetBotz 150 includes six sensor ports for monitoring input from APC environmental sensors and other third-party sensors.
Depending on the connected appliance, the Pod 150 can be cascaded for more sensor inputs. You can connect the NetBotz 150 to one of the following appliances: NetBotz Rack Monitor 200 (NBRK0200), NetBotz Rack Monitor 450 (NBRK0450), NetBotz Room Monitor 455 (NBRK0451, NBWL0455, NBWL0456), or NetBotz Rack Monitor 550 (NBRK0550, NBRK0570). The Rack Sensor Pod 150 cannot be used with a NetBotz Room Monitor 355.
6 Optional sensors: Add sensors to compatible NetBotz Appliances for monitoring temperature, humidity, fluid, vibration, dust particles, etc.
A-Link communication port: Deployment flexibility allows sensor pods to be up to 3280 Ft (1000 meters) from a compatible NetBotz appliance.
RJ-45 sensor connection type: Automatically detected by compatible NetBotz appliances and easily extended with standard CAT5/6 cable to 100 feet.
Unique identifiers: Customize each sensor with a differentiating name and location.
Mounting: Includes horizontal, vertical and toolless-mount capabilities.
Operating Environment: 32 - 113 °F (0 - 45 °C)
Storage Temperature: 5 - 149 °F (-15 - 65 °C)
Operating & Storage Humidity: 0 - 95%
Operating Elevation: 0-10000 feet (0-3000 meters)
Storage Elevation: 0-50000 feet (0-15000 meters)
Electrical Input / Draw: 24 VDC; 50–175 mA - Provides supplemental power for high-current load configurations. Supplemental power is not required for most system configurations.
Standard warranty: 2 years repair or replace
Compliance: CE, FCC Part 15 Class A, ICES-003 Class A, VCCI Class A, EN 55022 Class A, EN 55024, AS/NZS CISPR 22
Standard Lead Time: Usually in Stock
Price: $389.99 NOW: $344.05 Save: $45.94
Rack Units
1U
Dimensions
1.74"H x 13.25"W x 1.74"D)
Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor Cable (NBES0305). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
If a sensor cable is not long enough, use an RJ-45 coupling (provided with some sensors) and standard CAT-5 cabling to extend the cable up to 15 m (50 ft) for a Temperature/Humidity Sensor (AP9335TH) or a Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other supported sensors.
Includes: NetBotz Rack Sensor Pod 150, Rackmount Brackets, Temperature/Humidity Sensor (AP9335TH), 8-32 x 1/4-in Phillips head screws, A-Link terminator, Documentation CD, Installation Guide
APC Temperature Sensor - 13 Ft APC AP9335T NetBotz is a 13 Ft universal sensor that monitors temperature in your Data Center or Network Closet.
$170.24
APC Temperature & Humidity Sensor - 13 Ft APC AP9335TH NetBotz is a 13 Ft universal sensor that monitors temperature and humidity in your Data Center or Network Closet.
$136.90
NetBotz Spot Fluid Sensor - 15 ft. APC NBES0301 NetBotz 15 Ft universal Sensor that provides early detection of fluid in your Data Center or Network Closet in a specified location.
NetBotz Vibration Sensor - 12 ft. APC NBES0306 NetBotz is a 12ft universal Sensor that detects vibration in racks that may indicate movement of IT assets.
NetBotz Dry Contact Cable - 15 ft - For 3rd Party Sensors APC NBES0304 NetBotz is a 15ft universal Sensor that monitors third-party dry contact state sensors. With this cable you can now use many standard dry contact–based sensors (such as motion detectors, moisture detectors, or glass-break detectors) as external NetBotz sensors.
Power Supply 100-230 VAC/24 VDC - IEC C7 External power supply that provides additional power to SmartSlot Expansion Chassis and select NetBotz applications I.E. for cascading multiple the APC POD 150s