AC Power Monitor with Relay - 12A - Reports AC Voltage, Frequency, Power, and Current.
- Monitors Power from one AC inlet to one AC outlet, between 50~250VAC and 47~63Hz.
- Monitors the number of swells, sags, and spikes.
- Monitors swell and sag duration of 0.1 second to 1 minute.
- Includes Relay with configurable disconnect settings: threshold reboot, or manual reboot.
- Accuracy
- Voltage accuracy: ± 1%
- Frequency accuracy: ± 1%
- Current accuracy: ± 1%
- Outlet Max load rating (continuous): 12A rated load, 15A maximum.
- Capable of measuring current surges from 300 mA to 20A.
- User defined minimum and maximum voltage and power thresholds.
- Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
- Cables included: One country-specific IEC 320 C13 line cord, and one IEC 320 C14 to IEC 320 C13 cord set for connection to AC load.
- Supports CAT5/5e/6 cable up to 1,000 ft. (305 m).
- Dimensions (WxDxH) in: 7.0x5.5x1.65 (178x140x42 mm).
- Weight: 1.6 lbs (726 g).
- Powered by ENVIROMUX-2D/5D/16D.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
- Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.
ENVIROMUX-ACLM - Installation Manual (PDF) Formerly the NTI ENVIROMUX-ACLM-P12. |
Price: $345.00 NOW: $315.00 Save: $30.00 |