Rittal TopTherm Rack Top Mount AC Unit - 115V, 770 W (2627 BTU)

Rittal 3359510 (3359.510) TopTherm Blue roof-mounted cooling unit features a nano-coated condenser, a integral electric condensate evaporation, drilling template and assembly parts. TopTherm roof-mount units are constructed of sheet steel (RAL 7035 - Light Grey) for durability with an integral e-Comfort controller for temperature control (factory setting 95°F / 35°C).

The Rittal 3359510 Energy-efficient cooling unit supports plug-in terminal strip connection, with a transformer circuit-breaker, and 100% power duty cycle for optimal performance. It operates at temperature range of 10 - 55 deg C.

  • Total Cooling Output (DIN EN 14511): 0.77 kW @ 50 Hz, 0.79 kW @ 60 Hz (L35/L35)
  • BTU Capacity (L35/L35 60 Hz.): 2695 BTU
  • Air Throughput (unimpeded):
    External circuit: 535 CFM (910 m3/h)
    Internal circuit: 259 CFM (440 m3/h)
  • Temperature Control: e-Comfort controller (factory setting 95 °F / 35°C)
  • Temp. Setting Range: 68 - 131°F (20°C - 55°C)
  • Input Power: 115 V 50 Hz/60 Hz - Plug-in terminal strip
  • Approvals: UL, cUL, CSA, TUV Leistung, TUV Sicherheit, External circuit IP 34, Internal circuit IP 54.
  • Warranty: 2 Years

Air conditioners with comfort controller may be integrated into a monitoring system with an optional interface card 3124.200 (RS 232, RS 485, RS 422 and PLC interface), for remote monitoring and control.

3359.510 Diagram

Please Note: this item cannot be returned. Make sure to size your cooling and power requirements correctly before ordering. Standard manufacturer warranty still applies.

Standard lead time is 1-15 business days for shipment.

Rittal 3359510 - Click to enlarge

Rittal
Price: $5,566.58
NOW: $5,352.49
Save: $214.09
Free Project Evaluation
Shipping
Shipping Method
Dock-to-Dock Ground Service (+$130.00)
Ground if you do not have a Loading Dock (+$190.00)
Optional Shipping Services
Server Racks Online Extra Options None
Lift gate (+$65.00)
Inside Delivery (+$150.00)
Inside Delivery and Lift Gate (+$215.00)

Flexible performance
Only 3 mounting cutouts for 6 different output categories in 28 design versions.

Targeted air routing in the enclosure
The internal air circulation is targeted and effective: The heated air is extracted centrally. Air exhaust occurs in the four corners, based on your specific requirements.

Flexible condensate management
All roof-mounted air conditioners with comfort controller are equipped with a condensate warning feature. A condensate pump and condensate evaporator may be integrated.


Download IconTopTherm Roof-mount Manual (PDF)
Rittal Manufacturer's Warranty for Climate Control Products (PDF)

Energy-efficient Blue e roof-mounted cooling units in output categories from 500 W to 4,000 W, with integral e-Comfort controller, RiNano coating on the condenser and electrical condensate evaporation as standard.

Protection Category IP to IEC 60 529:
- External circuit IP 34
- Internal circuit IP 54

Rittal 3359510 Includes:
- Nano-coated condenser
- Integral electric condensate evaporation
- Fully wired ready for connection (plug-in terminal strip)
- Assembly parts

3359.510 Cooling Chart @ 50 Hz

3359.510 Cooling Chart @ 60 Hz

Rittal 3359510 / 3359.510 Specifications

Mechanical 
Height16.42" (417mm)
Width23.5" (597mm)
Depth14.96" (380mm)
Weight81.57 lbs. (37 kg)
MaterialSheet steel
Contact us for Stainless steel option
ColorRAL 7035 (Light Grey)
Form FactorRoof-Mount
Cooling
BTU Capacity (L35/L35 60 Hz.)2695 BTU
Total cooling output to DIN EN 14511:L 35 L 35 at 50 Hz: 0.77 kW
L 35 L 35 at 60 Hz: 0.79 kW
L 35 L 50 at 50 Hz: 0.52 kW
L 35 L 50 at 60 Hz: 0.47 kW
Air throughput:
*unimpeded air flow
External circuit: 535 CFM (910 m3/h)
Internal circuit: 259 CFM (440 m3/h)
Temperature control:e-Comfort controller (factory setting 95°F / 35°C)
Temperature range:Operation (environment): 50 - 131°F (10°C - 55°C)
Setting range: 68 - 131°F (20°C - 55°C)
Refrigerant/cooling medium:Refrigerant: R134a
Quantity: 14.11 oz. (400 g)
Permissible operating pressure (p. max.):4006 psi (28 bar)
Power 
Rated operating voltage:115 V, 50 Hz/60 Hz
Type of electrical connection:Plug-in terminal strip
Duty cycle:100 %
Power consumption Pel:L 35 L 35 at 50 Hz: 0.33 kW
L 35 L 35 at 60 Hz: 0.43 kW
L 35 L 50 at 50 Hz: 0.49 kW
L 35 L 50 at 60 Hz: 0.42 kW
Rated current (max.):At 50 Hz: 5.6 A
At 60 Hz: 7.4 A
Start-up current max.:At 50 Hz: 18.4 A
At 60 Hz: 18 A
Pre-fuse:Transformer circuit-breaker: 11 A...16 A
Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511:2.28
Approvals- UL 484 (Standard for Room Air conditioners),
- cUL
- CSA C22.2 No.236 (Standard for Heating and Cooling Equipment),
- TUV-Geprufte Leistung
- TUV-Geprufte Sicherheit
Protection Category IP to IEC 60 529:- External circuit IP 34
- Internal circuit IP 54
Warranty2 Years



Interface Board for e-Comfort Controller Equipment - (RS 232, RS 485, RS 422 and PLC interface)
$405.77
Interface Board for e-Comfort Controller Equipment - (RS 232, RS 485, RS 422 and PLC interface)
Interface Board for e-Comfort Controller Equipment - (RS 232, RS 485, RS 422 and PLC interface)

2x Polyurethane Stoppers - Cover unused air outlets - for 3359.xxx, and 3382.xxx
$40.63
2x Polyurethane Stoppers - Cover unused air outlets - for 3359.xxx, and 3382.xxx
2x polyurethane foam stoppers to cover any cold air outlets that are not required. Stoppers are used with roof-mounted cooling units (3359.xxx, and 3382.xxx) and air/water heat exchangers.

Primary/secondary cable For SK BUS system
$415.22
Primary/secondary cable For SK BUS system
Primary-secondary cable For SK BUS system

32ft (10m) Condensate hose  - 12 x 2mm thick
$121.16
32ft (10m) Condensate hose - 12 x 2mm thick
32ft (10m) Condensate hose - 12 x 2mm thick

RiDiag II - Cooling Unit Monitoring Software
$467.83
RiDiag II - Cooling Unit Monitoring Software
For the diagnosis, maintenance and long-term data capture of TopTherm units with e-Comfort controller. RiDiag logs equipment data and prepares an error list.

Air duct adaptor for air duct system and shallow air duct system
$121.59
Air duct adaptor for air duct system and shallow air duct system
Air duct adaptor that allows the connection of the spigot from which air is supplied by the cooling unit to the air duct system.

Air duct system For roof-mounted cooling units and roof-mounted air/water heat exchangers
$392.62
Air duct system For roof-mounted cooling units and roof-mounted air/water heat exchangers
Cold air can be routed directly to specific areas of the enclosure using the air duct system.

Door-operated switch
$92.66
Door-operated switch
Door-operated switch

Filter Mats for Cooling Units - 3273.xxx, 3382.xxx, 3383.xxx, 3384.xxx, 3385.xxx, and 3359.xxx
$72.93
Filter Mats for Cooling Units - 3273.xxx, 3382.xxx, 3383.xxx, 3384.xxx, 3385.xxx, and 3359.xxx
Filter mats may be used for extreme conditions, particularly when cooling units are used in a dusty environments.

Metal Filters for Cooling Units - 3273.xxx, 3382.xxx, 3383.xxx, 3384.xxx, 3385.xxx, and 3359.xxx
$316.22
Metal Filters for Cooling Units - 3273.xxx, 3382.xxx, 3383.xxx, 3384.xxx, 3385.xxx, and 3359.xxx
Particularly when cooling units are used in a dusty and oily environments, it is advisable to use washable metal filters.

Quick-change frame for roof-mount cooling units - 3359.xxx and 3382.xxx
$573.27
Quick-change frame for roof-mount cooling units - 3359.xxx and 3382.xxx
Use the quick-change roof-mount frame for easily removing a cooling unit during servicing work - shorted assembly times and hence minimized downtime. Includes Integral drainage through eliminiating ingress of oil.