Mechanical | |
Height | 3.4 in. (8.64 cm.) |
Width | 17.4 in. (44.2 cm.) |
Depth | 25 in. (64 cm.) |
Weight | 74.5 lbs. (33.8 kg.) |
Environmental | |
Heat Dissipation (BTU) | Line: 588, Bat: 3,071 |
Audible Noise | Max 45 dBA |
Operating Temperature | 0˚C (32˚F) to +35°C (95˚F) |
Storage Temperature | -15˚C (5˚F) to +50˚C (122˚F) |
Relative Humidity | 20–95% non-condensing |
Altitude | Up to 10,000 ft (3000M) without de-rating |
Electrical Input | |
Connection | L5-30P |
Input Cord | 6 ft. (1.8 m) |
Input Voltage Range | 80-151V (* The high and low thresholds can be user adjusted using the downloadable UPS Configuration tool) |
Nominal Voltage | 120 VAC |
Frequency | 50/60 Hz (auto-sensing) |
Frequency Range | 47–70 Hz for 50 Hz operation 56.5–70 Hz for 60 Hz operation |
Nominal Current | 25.4 A |
Breaker Ratings | 30A |
Electrical Output | |
Output Receptacles | (6) 5-20R, (1) L5-30R |
On Utility Voltage Regulation | 102-132 Vac |
On Battery Voltage Regulation | -10%, +6% of nominal |
Voltage Wave Shape (On Battery) | Sine wave |
Power Factor | 0.9 |
Efficiency (on Battery) | 0.75 |
Frequency Regulation | 0.1 Hz |
Transfer Time | 1 to 4 ms, typical |
Load Crest Factor | 3:1 |
Load Segments | Two individually controlled output receptacles |
Battery | |
Maximum Number of Battery Packs | 4 |
Battery Type | 12V/9 Ah; sealed, lead-acid; maintenance free |
Half Load Runtime (in mins) | 10 |
Full Load Runtime (in mins) | 3 |
Battery Replacement | Hot-swappable internal batteries |
Battery Voltage | 12V |
Start On Battery | Allows start of UPS without utility input |
Communications | |
LEDs | 13 status-indicating LEDs |
Communication Ports | Serial Port RS-232 (RJ45) ports; USB Port As standard (HID). RS-232 and USB 6-ft communication cables included |
Optional Communication Cards | ConnectUPS-MS network management card and ModBus |
Power Management Software | Eaton Software Suite CD-ROM (bundled with UPS) |
General | |
Topology | Line interactive |
Color | Black |
Rating (VA/Watts) | 2880/2700 |
Diagnostics | Full system self-test at power up |
Efficiency | >94% |
Rail Kit Included | Towers stands and 4-post rail kit included with all units |
Warranty | Three-year factory warranty with online product registration |
Remote Emergency Power off (REPO) | Rear deck emergency stop connector (for remote on/off and power off) |
Standards | |
Safety markings | UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1) |
EMC Markings | FCC Part 15 subpart B Class A |
Markings | UL; cUL |