Electrical Input | |
Nominal Voltage | 120 V Models are 110 V or 120 V user-selectable; 230 V models are 220 V, 230 V or 240 V user-selectable |
Input voltage ranges for user-selectable voltages | +20% for nominal voltage at full load |
Operating Frequency | 50/60 Hz, Auto-sensing |
Frequency Range | 46-65 Hz |
Electrical Output | |
On Utility Voltage Regulation | -10% to +6% of nominal |
On Battery voltage Regulation | ±5% RMS |
Voltage Wave Shape (on battery) | Sine Wave |
Over Current Protection | Electronic current limit |
Communications | |
User Interface | LED status display with AC power on, load Group, Overload, On Battery and General Alarm indicators, Site Wiring Fault Indicator on rear panel for low volt models. |
Audible Alarms | For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault |
Network transient Protector | UL 497 A, In/out jacks RJ45 (high voltage models network protection) & RJ11 (low voltage models modem protection) |
X-Slot Optional Communication cards | ConnectUPS-X Web/SNMP/xHub Card; USB card ; Relay card |
Standard Communications | 1 x RS-232 Serial Port & 1 x xUSB Port |
Cable | 6-foot communications cable included |
Power Management Software | Powerware Software Suite CD-ROM (bundled with UPS) |
Battery | |
Battery Type | Sealed, lead-acid; maintenance free |
Battery Replacement | Hot-swappable internal batteries |
Battery Recharge | < 3 hours to 90% capacity |
Start-On-Battery | Allows UPS operation without utility input |
General | |
Diagnostics | Self-test @ power up |
Transfer Time | 2-4ms typical |
Overload (normal operation) | 110% overload, shutdown after 3 minutes; 150% overload, shut down 10 cycles |
Environmental | |
Operating Temperature | 0 to 40° C (32 to 104° F) |
Safety Markings | 120 V Models: UL; cUL 230 V Models: C-Tick; CE, TUV, cUL, UL |
Safety Conformance | 120 V Models: UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1) 230 V Models: UL1778, UL 497A (data line only); cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and IEC 60950 |
EMC Markings | 120 V Models: FCC Part 15 subpart J Class A, ICES-003; 230 V Models: EN 50091-2. FCC Part 15 subpart J Class A, ICES-003 |
Surge Suppression | ANSI C62.41 Category A (formerly IEEE 587) |
Audible Noise | < 40 dBA typical |
Altitude | Up to 3000M (10,000 ft) without derating |